1.  Emergency eyewash and shower equipment shall be on the same level as the hazard and accessible for immediate use in locations that require no more than 10 seconds for the injured person to reach. The path of travel must be free of obstructions. If both eyewash and shower are needed, they shall be located so that both can be used at the same time by one person.

  •   T8 CCR, Section 5162(c)
  •   2013 CPC, Section 416.4

The average person covers a distance of approximately 55 ft. in 10 seconds when walking at a normal pace. The physical and emotional state of a potential victim (visually impaired, with some level of discomfort/pain, and possibly in a state of panic) should be considered along with the likelihood of personnel in the immediate area to assist. Other potential hazards that may be adjacent to the path of travel that might cause further injury should be considered.

  • ANSI Z358.1-2014, Appendix B5

2.  One intervening door can be present so long as it opens in the same direction of travel as the person attempting to reach the emergency eyewash and shower equipment and the door is equipped with a closing mechanism that cannot be locked to impede access to the equipment (i.e., the door is a panic door). Where the hazard is corrosive, consult with EH&S.

  • Good Practice per Stanford University EH&S
  •  ANSI Z358.1-2014, Appendix B5