1. No obstructions shall be located within 16 inches from the center of the spray pattern of the emergency shower facility. Note: The eyewash is not considered an obstruction.
- T8 CCR, Section 5162(c)
- ANSI Z358.1-2014, Section 4.1.4
- 2013 CPC, Section 416.1
2. No electrical apparatus or receptacles (electrical outlets) shall be located within a zone measured 3 feet horizontally and 8 feet vertically of eyewash stations or showers. If a 120-volt outlet or receptacle is present within 6 feet of an eyewash or shower, it shall be equipped with a Ground Fault Circuit Interrupter (GFCI).
- NEC
- Good Practice per Stanford University EH&S
This prevents potential electrical hazards posed when the water generated by the activated emergency eyewash/safety shower is in proximity to live electrical equipment.