1.  Flammable Liquid Storage Cabinets shall NOT be located near exit doorways, stairways, or in a location that would impede egress.

CCR, Title 24, Part 9, Section 7902.5.5

2.  Flammable Liquid Storage Cabinets must NOT be wall mounted.

Good Practice per Stanford University EH&S

Wall mounted cabinets are not UL Listed or Fire Marshal Approved.

3.  Laboratory design must ensure that Flammable Liquid Storage Cabinets are NOT located near an open flame or other ignition source.

Good Practice per Stanford University EH&S

An open flame or other ignition source could start a fire or cause an explosion if an accident or natural disaster brought the ignition source and flammable liquids or vapors together.